• Year
  • 1987
  • Category
  • Power supply/conditioner or battery or charger 
  • Radiomuseum.org ID
  • 317700

 Technical Specifications

  • Number of Transistors
  • Semiconductors present.
  • Semiconductors
  • Wave bands
  • - without
  • Power type and voltage
  • Alternating Current supply (AC) / 205 - 275 Volt
  • Material
  • Metal case
  • from Radiomuseum.org
  • Model: Mini Line Tamer MLT 160 - Ferguson Transformers Pty. Ltd
  • Shape
  • Boatanchor (heavy military or commercial set >20 kg).
  • Dimensions (WHD)
  • 190 x 240 x 255 mm / 7.5 x 9.4 x 10 inch
  • Notes
  • The MLT series of constant voltage tamers are designed to provide a relatively constant output voltage when there are substantial fluctuations in supply voltage.
    It is used to isolate the critical load from both common-mode and transverse-mode electrical noise. The mini line tamer may be considered as a combination of voltage regulator and a noise filter. The basic component is a ferro-resonant (constant voltage) transformer.

    Features:

    Input Voltage range 205-275 V, 50 Hz
    Regulating output ±3% for ±15% input
    Output Voltage 250 V, 50 Hz
    Common-Mode rejection > 120 dB frequencies up to 1 MHz
    Transverse-Mode rejection > 60 dB frequencies 10 kHz to 1 MHz
    Sinusoidal Output 3% harmonic content
    Rating 160 VA cool & efficient operation typically 90% at full load

     

  • Net weight (2.2 lb = 1 kg)
  • 10.1 kg / 22 lb 3.9 oz (22.247 lb)
  • Mentioned in
  • - - Manufacturers Literature (1987 Catalogue)
  • Author
  • Model page created by Gary Cowans. See "Data change" for further contributors.